SR EN 50425:2008
Switches for household and similar fixed electrical installations - Collateral standard - Fireman's switches for exterior and interior signs and luminaires
This clause of Part 1 applies with the following modifications: Replacement of the first paragraph: This collateral standard applies to fireman's switches used for the breaking of the low voltage circuits for exterior and interior signs and luminaires e.g. neon signs for a.c. only with a rated voltage not exceeding 440 V and a rated current not exceeding 125 A. NOTE 1 The working voltage for the signs and luminous-discharge-tube installations is higher than 1 kV but lower than 10 kV and these should be in accordance with EN 50107 series. Renumbering of the subsequent notes. Replacement of the 6th paragraph and the new Note 6 by: Fireman’s switches complying with this standard are suitable for use between –20 °C and +70 °C. NOTE 6 Fireman’s switches are designed for overvoltage category III and used in environment of pollution degree 2 according to EN 60664-1.
Status :
Withdrawn
Approval date : 7/31/2008
Publish date : 8/2/2008
Withdrawal date : 2/22/2015
Number of pages : 24
ICS : 29.120.40 Switches
Technical Committee : 11 - Electrical accessories
- Normative reference SR EN 50107-1:2003
- Normative reference SR EN 50107-2:2006
- Normative reference SR EN 60669-2-4:2005
- Normative reference SR EN 60669-1:2002
- Normative reference SR HD 384.5.51 S2:2004
- Normative reference SR EN 50107-1:2003/A1:2004
- Normative reference SR EN 60669-1:2002/C91:2005
- Normative reference SR EN 60669-1:2002/A1:2003
- Normative reference SR EN 62262:2004
- Replaced by SR EN 60669-2-6:2013