SR EN 50191:2011

Erection and operation of electrical test equipment

1.1 This European Standard is applicable to the erection and operation of fixed and temporary electrical test installations. 1.2 Compliance with this European Standard is not necessary, if contact with live parts presents no danger. This is the case when one of the following conditions is satisfied at live exposed points: a) the voltage at frequencies above 500 Hz does not exceed 25 V a.c. or 60 V d.c. and complies with the requirements for SELV or for PELV in accordance with HD 60364-4-41; b) in case of voltages at frequencies up to 500 Hz exceeding 25 V a.c. or 60 V d.c., the resultant current through a non-inductive resi¬stance of 2 k? does not exceed 3 mA a.c. (r.m.s.) or 12 mA d.c; c) at frequencies above 500 Hz the national determined current and voltage values shall be applied. If there are no national requirements determined reference values for permissible body currents and contact voltages can be taken from Table A.1; d) the discharge energy does not exceed 350 mJ. NOTE 1 Even though compliance with the requirements of this European Standard is not necessary, if one

32.55

Status : Valid
Approval date : 8/31/2011
Number of pages : 24
ICS : 17.220.20 Measurements of electical and magnetic quantities,19.080 Electrical and electronic testing,29.020 Electrical engineering in general
Technical Committee : 8 - High-voltage switchgear and controlgear and testing techniques, instrument transformers

Relations with other standards: